BENNING PV-Inverter Range TLS

Energy Production and Storage of the Latest Generation

Energy production and storage of the latest generation

BENNING PV Inverter TLS 5.1

Special characteristics of the single phase TLS inverters

  • 2 MPP trackers
  • Plug & Play installation
  • up to 5,700 Wp recommended DC power
  • relay contact for self consumption optimisation
  • integrated data logger and web server
PV Inverter TLS 5.1
PV Inverter TLS 5.1
DC Input: BENNING PV Inverter TLS 5.1
Recommended DC power (+15 % acc. ISE) 5700 W
Maximum input voltage 850 V
Minimum input voltage/Start input voltage 180 V / 200 V
Minimum input voltage* 180 V
MPP voltage range 250 - 720 V
Rated input voltage 680 V
Maximum current per input (A/B) ** 12 A
Maximum short circuit current per input 16 A
Start feeding-in at 20 W
Number of independent MPP inputs 2
Strings per MPP input 1
DC terminal type SUNCLIX
DC Overvoltage category III
AC Output: BENNING PV Inverter TLS 5.1
Rated output power (230 V / 50 Hz, cos(φ)=1) 4600 W
Maximum apparent AC power 4600 VA
AC connection L / N / PE
AC nominal output voltage range 230 V +/-20 %
Power factor range, adjustable cos(φ) 0,9 ind. … 1 … 0,9 kap.
Operating range at nominal frequency 50 Hz 50 Hz / 47,5 Hz - 51,5 Hz
Maximum output current 22 A
Maximum short circuit current 22 A
Maximum permitted fusing Circuit breaker 16 A (TLS 5.1 - 32 A), characteristic B
Distortion factor at cos(φ) = 1 < 3 %
Self-consumption at night < 2 W
AC Overvoltage category III
Efficiency BENNING PV Inverter TLS 5.1
Maximum efficiency 97,8 %
European efficiency 97,2 %
Protection and protective devices: BENNING PV Inverter TLS 5.1
Topology transformerless
Protection class I
Earth fault detection integrated
Residual current monitoring integrated, sensitive to universal current
Overload behaviour operating point adjustment
Overtemperature behaviour operating point adjustment
Input isolator integrated
Overvoltage protection-input integrated, type 3 as per EN61643-11
Overvoltage protection-output integrated, type 3 as per EN61643-11
Automatic disconnection device as per VDE 0126-1-1
Environmental conditions BENNING PV Inverter TLS 5.1
Ingress protection IP 65
Cooling concept fan-less
Operating temperature range -20°C – 60°C
Maximum ambient temperature at rated power 45°C
Climatic category 4K4H according to IEC 721-3-4 ***
Maximum operating altitude 2000 m above sea level
Noise emission ≤ 50 dB(A)
Standards and approvals BENNING PV Inverter TLS 5.1
EMC emission EN 61000-6-3: 2007
EMC immunity EN 61000-6-2: 2005
Equipment safety EN 62109-1, -2
Grid compliance VDE-AR-N 4105
General Data: BENNING PV Inverter TLS 5.1
Dimensions in mm (W x H x D) 360 x 506 x 190 (without plugs)
Weight (approx.) 26 kg
Features BENNING PV Inverter TLS 5.1
Display liquid crystal display, 128 x 64 pixel
Communication interfaces (internal) RS 485, USB, Ethernet, solar radiation, S0 as per DIN EN 62053-31 class B
Data storage 24 hours: 5-min values
30 days: hourly values
20 years: daily values
Relay contact 2 x potential-free contact

*) This value is valid if one input has exceeded the start input voltage.
**) It is permitted to exceed this limit as long as the maximum short circuit current is not exceeded.
***) The device is designed for an outdoor use. Direct sunlight and precipitation (rain, snow hail) hast to be avoided on site.

Technical changes reserved version of: 31.10.2014

Further information

Brochures
Case Studies
Certificates
Data Sheets
Instruction manuals
Soft- and Firmware

Technical Support
(After Sales Service)

Phone+49 2871 93 595
Email helpdesk@benning.de

Product Advice
Peter Hoeptner

Phone+49 2871 93 259
Email p.hoeptner@benning.de

Callback

In order to make this website optimally and continuously improve, we use cookies. By continuing to browse the site, you are agreeing to our use of cookies. For more information, see our privacy policy. Read more …